Application and Description:
These cables are used for internal wiring of switchboards and distribution boards at AC voltages up to 1000V or
DC voltages up to 750V. They are generally installed in ducts and are used for internal wiring of equipment with
an operating temperature of 90°C. They are suitable for use in public places (such as government buildings, etc.)
where smoke and toxic gases may cause threats to life and damage to equipment. This cable does not produce
corrosive gases when burned, which is particularly important for electrical equipment.
Standards and Approvals:
Cable Construction:
- Stranded flexible bare copper conductor
- Complies with VDE-0295 Cl 5, IEC 60228 Cl-5 BS 6360 cl. 5, HD 383
- Cross-linked polyolefin EI5 insulation
- LSOH - Low Smoke Zero Halogen
Technical Features:
- Working voltage: 300/500v (H05Z-K), 450/750v (H07Z-K)
- Test voltage: 2500 V
- Dynamic bending radius: 8 x Ø
- Static bending radius: 8 x Ø
- Working temperature during application: -15º C to +90º C
- Flame retardant: IEC 60332.1
- Insulation resistance: 10 MΩ x km
- Smoke density complies with EN 50268 / IEC 61034
- Gas corrosivity complies with EN 50267-2-2, IEC 60754-2
- Flame retardant test complies with EN 50265-2-1, IEC 60332.1
Cable parameters:
|
Number of cores x conductor cross-sectional area # x mm² |
Nominal insulation thickness mm |
Nominal outer diameter mm |
Nominal copper weight kg/km |
Nominal cable weight kg/km |
|
H07Z-K |
||||
|
1 x 1.5 |
0.7 |
3.5 |
14.4 |
24 |
|
1 x 2.5 |
0.8 |
4 |
24 |
35 |
|
1 x 4 |
0.8 |
4.8 |
38 |
51 |
|
1 x 6 |
0.8 |
6 |
58 |
71 |
|
1 x 10 |
1.0 |
6.7 |
96 |
118 |
|
1 x 16 |
1.0 |
8.2 |
154 |
180 |
|
1 x 25 |
1.2 |
10.2 |
240 |
278 |
|
1 x 35 |
1.2 |
11.5 |
336 |
375 |
|
1 x 50 |
1.4 |
13.6 |
480 |
560 |
|
1 x 70 |
1.4 |
16 |
672 |
780 |
|
1 x 95 |
1.6 |
18.4 |
912 |
952 |
|
1 x 120 |
1.6 |
20.3 |
1152 |
1200 |
|
1 x 150 |
1.8 |
22.7 |
1440 |
1505 |
|
1 x 185 |
2.0 |
25.3 |
1776 |
1845 |
|
1 x 240 |
2.2 |
28.3 |
2304 |
2400 |